Room Heating Calculator UK

Heating Formula:

\[ Q = U \times A \times \Delta T + 0.33 \times V \times ACH \times \Delta T \]

W/m²K
K
1/h

Unit Converter ▲

Unit Converter ▼

From: To:

1. What is a Room Heating Calculator UK?

Definition: This calculator estimates the heating power required to maintain a comfortable temperature in a room based on UK building standards.

Purpose: It helps homeowners, architects, and builders determine appropriate heating system capacity for residential and commercial spaces.

2. How Does the Calculator Work?

The calculator uses the formula:

\[ Q = U \times A \times \Delta T + 0.33 \times V \times ACH \times \Delta T \]

Where:

Explanation: The formula calculates both conduction heat loss through surfaces and ventilation heat loss through air changes.

3. Importance of Heating Calculation

Details: Proper heating calculation ensures energy efficiency, comfort, and correct sizing of heating systems to prevent under- or over-heating.

4. Using the Calculator

Tips: Enter the U-value, surface area, temperature difference, room volume, and air changes per hour (default 0.5 for UK homes). All values must be > 0.

5. Frequently Asked Questions (FAQ)

Q1: What is a typical U-value for UK homes?
A: Modern UK homes typically have U-values of 0.18-0.30 W/m²K for walls, 0.15-0.20 for roofs, and 1.4-2.0 for windows.

Q2: How do I determine the temperature difference?
A: Subtract the winter design external temperature (typically -3°C to +2°C in UK) from your desired internal temperature (usually 18-21°C).

Q3: What's a normal ACH value?
A: UK building regulations typically require 0.5 ACH for new homes, but older homes may have 1.0 or higher.

Q4: Why is the factor 0.33 used?
A: This accounts for the heat capacity of air (0.33 W/m³K) when calculating ventilation heat loss.

Q5: Should I add a safety margin?
A: Yes, consider adding 10-20% to account for heat loss through floors and other unaccounted factors.