Heat Load Formula:
From: | To: |
Definition: This calculator estimates the heat load required for radiant floor heating systems based on floor area, temperature difference, and U-value.
Purpose: It helps HVAC professionals and homeowners determine the heating capacity needed for efficient radiant floor systems.
The calculator uses the formula:
Where:
Explanation: The formula calculates the heat transfer rate needed to maintain the desired temperature.
Details: Proper heat load estimation ensures comfortable temperatures, energy efficiency, and correct system sizing.
Tips: Enter the floor area in sq ft, temperature difference (default 20°F), and U-value (default 0.05). All values must be > 0.
Q1: What is a typical U-value for floors?
A: Most floors have U-values between 0.03-0.07 BTU/(hr·ft²·°F), with 0.05 being common for well-insulated floors.
Q2: How do I determine the temperature difference?
A: Subtract the floor temperature from the desired room temperature (typically 20-25°F difference).
Q3: Why convert to watts?
A: Many radiant floor systems use electric heating elements rated in watts, or hydronic systems can be converted.
Q4: Does this include heat loss through walls/windows?
A: No, this calculates only floor heating needs. A complete heat loss calculation would include other factors.
Q5: How much should I oversize the system?
A: Consider adding 10-15% to the calculated load for safety margins and faster warm-up times.