Heat Load Formula:
From: | To: |
Definition: This calculator estimates the total heat generated in an electrical room from transformer losses, lighting, and panel loads.
Purpose: Helps electrical engineers and HVAC professionals determine cooling requirements for electrical equipment rooms.
The calculator uses the formula:
Where:
Explanation: All heat-generating components are summed to determine the total heat that needs to be removed from the space.
Details: Proper heat load estimation ensures adequate cooling capacity to maintain safe operating temperatures for electrical equipment.
Tips: Enter the heat contribution from each source in Watts. Values must be ≥ 0.
Q1: How do I find transformer losses?
A: Typically provided in manufacturer specifications or calculated as 1-2% of transformer rating.
Q2: What's included in panel load?
A: Heat generated by circuit breakers, busbars, and conductors (typically 3% of connected load).
Q3: Should I include safety factors?
A: Yes, consider adding 10-20% to the calculated heat load for design margin.
Q4: How does this relate to cooling requirements?
A: The heat load equals the minimum cooling capacity needed (in Watts or BTU/hr).
Q5: What about other heat sources?
A: For comprehensive analysis, include UPS systems, batteries, and external heat gains if significant.